Troubleshooting and Repairing a Faulty Condenser Fan Motor in a Rooftop HVAC Unit

Rooftop HVAC units contain multiple components that operate together to heat, cool, and circulate air through a commercial building. One critical element is the condenser fan motor, which pulls outdoor air across the condenser coil to reject heat. When this motor fails, it can severely impact the unit’s cooling capacity.

In this post, we’ll walk through the full troubleshooting and repair process for a faulty condenser fan motor in a rooftop HVAC unit. You’ll learn how to isolate the problem, replace the motor, and get the system fully operational again.

Whether you’re an HVAC technician or facility manager, understanding potential issues and solutions for these common commercial systems is valuable. Let’s get into the step-by-step breakdown!

Initial Testing and Diagnosis of the Condenser Fan Motor

We received a service call stating that one of the condenser fan motors was not operational in a rooftop HVAC unit. Upon arriving at the job site, an initial visual inspection revealed nothing obviously wrong. So we proceeded with diagnostic testing:

First, we opened the electrical control panel and verified that all fuses were intact and circuits showed no shorts to ground. This eliminated an immediate power supply issue.

Next, we accessed the system’s control board and put the rooftop unit into test mode. This allowed manually commanding the condenser fan motors on to isolate the failure.

When energized, all fan motors started except Circuit 2B. Through the process of elimination, this indicated Condenser Fan Motor 2B had failed. No further troubleshooting was needed to identify the fault.

At this point, we ordered a new replacement motor and corresponding contactor. We’d be ready to install once the parts arrived.

Step-by-Step Motor Replacement Procedure

After receiving the necessary parts, we were ready to replace the failed condenser fan motor:

1. Verify the Correct New Motor

Before disconnecting anything, we visually inspected the new motor to confirm it matched the original exactly, including electrical specs, connectors, and physical dimensions. This prevents wasted time trying to install the wrong component.

2. Disconnect Power and Lock Out Electrical

Occupational safety is critical. We shut down power to the rooftop unit and locked out the electrical disconnect switch to prevent any live circuits during service.

3. Document Original Fan Blade Position

To reassemble correctly, we noted the precise position of the fan blade on the original motor shaft. The new motor must align identically to avoid vibration or contact issues.

4. Detach Fan Blade from Failed Motor

After removing the shroud, we detached the fan blade from the damaged motor using a blade puller tool. With the motor seized, the blade would not slide off easily by hand.

5. Remove and Inspect Failed Motor

With the blade removed, we disconnected the failed motor’s wiring and mounting hardware to remove it from the rooftop unit. Inspection revealed extensive winding burnout as the culprit for failure.

6. Install New Replacement Motor

We mounted the new motor in place of the original. Great care was taken to properly align the shaft depth and keyway with the fan blade hub for smooth operation.

7. Reinstall Fan Blade onto New Motor

Using the reference marks made earlier, we reinstalled the fan blade onto the new motor at the precise original location to maintain proper condenser coil airflow.

8. Reapply Fan Shroud and Waterproofing

Once everything was securely reassembled, we replaced the motor shroud and sealed the top with foil tape. This protects against rainwater corrosion per the manufacturer’s recommendations.

Additional Repairs and Reassembly

With the motor swap complete, a couple of additional repairs were prudent while the rooftop unit was still disassembled:

Replace Corresponding Contactor

Since the motor failed, we recommended also replacing its corresponding contactor in the control panel. Arcing damage from excessive current draw can cause contactor pitting over time. This restores optimal connectivity.

Reconnect Wiring and Verify Circuits

We carefully re-landed all wiring on the contactor and motor terminals using nylon ferrules for maximum conductivity and insulation. Using an amp clamp, we verified proper current draw on all circuits before reenergizing the unit.

Restore Power and Exit Test Mode

With all repairs complete and electrical integrity verified, we closed up the control panel, exited test mode to restore automatic operation, and returned power to the rooftop unit.

Test Condenser Fan Operation

Before leaving the job site, we cycled the condenser fan bank on and carefully listened as each motor started in sequence to ensure proper direction and function. We also ran the unit through several operating modes to confirm normal response with our repair resolved the issue.

Conclusion

Servicing commercial rooftop units involves methodical diagnosis, repair procedures, and testing. When a condenser fan motor fails, a systematic process is required to restore cooling capabilities.

Key steps we covered included verifying the fault, matching components properly, carefully aligning parts during reassembly, and testing normal operation prior to leaving the job site.

While replacing a burned out motor is relatively straightforward, inattention to detail risks further damage or an unnecessary return trip if post-repair testing is neglected. Only by confirming normal system response across all operating modes can you truly consider the job complete.

Hopefully this overview better equips HVAC technicians to smoothly troubleshoot and fix failed condenser fan motors in packaged rooftop units when the need arises. Keeping these common commercial AC systems running at peak performance ensures ongoing comfort and operational reliability for building occupants.